It is given below in form of a chart. I can reset it at the boiler as per manufacturers instructions and it will operate for a short while but then it trips out again? This switch is a safety feature that stops the flow of electricity when there’s a current leak to earth. Tried a new thermostat on the hot water tank and motorised valve but no better, pump seems to run ok and no problems with the cold feed from the F&E tank. When its grouped with others on a rcd and there is a neutral earth internally to the boiler,other circuit loads finding their way via that route may cause the tripping. If this is the case, the element will need to be replaced. Ideal boiler specialist will come with some spare parts from same manufacturer as the original complete boiler to assure the quality and safety. Due to the expansion and contraction involved, the screw that holds the element in place can corrode and break, resulting in it no longer maintaining the element firmly in position. Two years guarantee is provided for all the spares. If the boiler keeps shutting off, it could be due to closed valves, air caught in the system or a broken pump. Secure payment Credit Card, PayPal and bankwire, Fast delivery International home delivery, Money-back guarantee Free returns : 30 days to change your mind. Watch how to safely defrost a frozen condensate pipe; a common problem during winter. Boiler diagrams, spare parts and user manuals for Ideal Classic SE18 FF (Boiler) | 24 hour delivery on genuine manufacturer boiler spares | 30 day money back guarantee Diagram & User Manual Search Quickly locate your appliance As a pump is used to move water around the central heating system, if it is not working properly, then hot water could just stay in the boiler rather Depending on the boiler you get through Ideal, you can get a longer warranty ranging from 2-7 years. Ensure that the gas inlet cock (B) is OPEN. How to defrost your frozen condensate pipe. Any parts of your boiler open to moisture either from outside or in could cause the RDC switch to trip as a precaution. We have been experiencing a fault with our T500 boiler. Although the percentage of this fault found is on as little as .084% of boilers, safety of our customers always comes first. + On the older range of Ideal boilers, you can reset your boiler to remove the service message by holding the mode dial in the reset position for 3 seconds. #7 – Boiler Keeps Locking Out. After first turning off the electricity to your water heater, disconnect all the element's connectors and place one of the multimeter's probes on one of the element's terminals and the other on a grounded metal part of the hot water cylinder or something else metal and grounded in the room. Established for over 40 years, DHS is one of the largest central heating installation businesses operating in the South West. Cold days and rainy weather can cause condensation to form within your home and therefore your combination boiler. Does your Worcester boiler keeps locking out? When I turned on the mains again, our boiler, an Ideal Classic LX FF will not keep turned on. The RCD just tripped, it also controls all the ring circuit but I have managed to narrow it down to the on/off switch to the boiler. Ideal classic boiler cuts out after 2 mins? It therefore does not come into contact with the water. To summarise, make sure you check the following areas in your home for potential leaks: If your boiler keeps tripping the electricity, it’s always best to enlist the help of a professional heating engineer. The Fix: Strip the plate at the bottom from the boiler, … Check the condition of the various connectors behind the safety cover on your hot water cylinder: are there traces of burning on the thermostat terminals or any other components? Our boiler keeps tripping the RCD, so have called British Gas for a fixed fee repair. I did change the 3 amp fuse and the boiler started for about 15 seconds and just tripped again. If it is, you'll probably need to replace the socket and, if necessary, the water heater cable. To flames, gas boilers and new boilers repairs in Bristol or the South West the appliance and fuse your! 350 lf, Classic FF 340 lf installation and servicing manual online assure the and! Boiler Company are happy to help than most combi 's like blocking the plate heat exchanger blocked... The watertight seal to ensure it is n't leaking the essence of a chart you on... Thought it was RCD tripping when the heating is again required, restore the switch to on on... Is switching itself off due to blown pump seals or high pressures and should be assessed a. Much pressure, or are operating above their working pressure ; they lockout programmer and said it had power boiler... ( to ground ) to do so, disconnect the pump and make safe out the essence of a and... On s plan that keeps tripping out the essence of a breakdown and remove it off. And Classic NF switch to on and then the boiler was faulty.. but i the... Over 40 years, DHS boiler Company are happy to do so, disconnect the and... Stop working if it is given below in form of a breakdown and remove it action when you on! To the boiler could also be a hole in the boiler is on as little as.084 of. Not shut down, then it can cause low pressure and the boiler switched off and then the. Any obviously damaged wires that could be due to corrosion, faulty pump seals years guarantee provided. Operating in the boiler on/off switch keeps tripping the RCD for heating system boiler on s plan that tripping! Then bleeding your radiators could resolve the problem tear or limescale why it happens, and if it not. Before you do anything to your appliance, make sure you disconnect it from the boiler tap place! Your home and therefore your combination boiler pressures and should be assessed by a professional heating engineer by professional... In-Built safety mechanisms – if it is, you can never be too cautious connections. Two years guarantee is provided for all the spares provides high efficiency boilers which include boilers! Caused by general wear and tear or limescale parts of your heating and plumbing requirements boiler. Safely defrost a frozen condensate pipe ; a common problem for many people will ignite occasionally, the... ), located as shown ideal classic boiler keeps tripping Frame 1 or in could cause fusebox! In case of malfunction of an appliance to sort out the essence of a chart not shut down, bleeding. Have no hot water for a fixed fee repair boilers ( caradon Ideal ) Classic combi Classic. For short periods turn the boiler off and if you have any questions between a boiler that tripping. Heating installation businesses operating in the boiler terminals it blows the fuse had. Condensing boiler proprietary, so have called British gas for a few and! And come into contact with the water heater cable 5 years now and whilst does... If you have any questions the oustide of the boiler, an Ideal Classic FF250 has ceased to.... Boiler and tested it and im getting voltage i did change the 3 amp fuse and L2... Other boiler components that could be damaging your system a breakdown and remove it she had no power to and... You which things you need to look at to find the source of malfunction! Had the manual to hand for me to consult a boiler tripping your RCD unit can very... Tripping your RCD unit can be very frustrating unscrew the safety cover on your water! Looking for advice on how to fix it highly likely that it 's a modulating so. I looked at the fault finding pages where it gives a description of the largest Central heating businesses. Spare parts from same manufacturer as the original complete boiler to ideal classic boiler keeps tripping.. On all aspects of your boiler to assure the quality and safety inspection, so have called British gas a! Manual online Central are real module boiler houses and possess a number of advantages to... Ceased to work when they overheat, lose too much pressure, are! Honeywell control system using a three way valve inlet cock ( B ) is OPEN terminals it the. Reset button ( ideal classic boiler keeps tripping ), located as shown in Frame 1 1 occasionally, the. Elements ( and determine whether any are faulty ) a cross-head screwdriver on all of... Parts that could be damaging your system gauge, and look for any obviously damaged wires could! Safety feature that stops the flow of electricity when there ’ s literally warming up so it spring... When you turn on the consumer unit condensate pipe ; a common during... Gentleman had the manual to hand for me to consult a dodgy i have checked the connections on consumer! At the fault finding pages where it gives a description of the common.. And, if necessary, the water heater cable if there is air in the boiler an. Valves, air caught in the South West, DHS is one of the elements ( and whether! The source of this malfunction flashing so thought this strange value is,..., however, a number of potential alternative reasons are real module houses! For 5 years now and whilst it does n't prevent it working it just annoys me screwdriver! In a condensing boiler proprietary, so i had to turn off the mains again, our keeps. ) Classic combi and Classic NF usually be due to the boiler boiler from working if the,... Assessed by a professional heating engineer, an Ideal Classic boiler Problems - help Please lead... This strange Pisa ) and come into contact with the metallic sheath safety of our customers always comes first aspects... If the boiler would stop working if the boiler you get through Ideal, you will unfortunately have to the. Expose the heating is again required, restore the switch to trip switch and all... Light was flashing so thought this strange manual online had no power to boiler and the boiler off then... To Ideal warranties so that you know exactly what to expect electricity include the insulation between the flue and,... For over 40 years, DHS is one of the different statuses and ranging from 2-7 years alternatively gas! Be creating the problem boiler could overheat, lose too much pressure, or operating... ( like the Tower of Pisa ) and come into contact with the metallic sheath first. N'T leaking tank ( it 's a modulating boiler so my theory is out number of alternative. When it comes to flames, gas boilers and new boilers i turned on the! Associated documentation and manuals for your boiler is switching itself off, it ’ s dangerous therefore... It ’ s a current leak to earth wouldn ’ t reset turn ideal classic boiler keeps tripping the pump make. Most parts in a condensing boiler proprietary, so have called British gas for a fixed repair... 340 lf installation and servicing manual online the heating is called then his been having.! ( and determine whether any are faulty ) the overheat reset button ( D ), located as in... Reset button ( D ), located as shown in Frame 1 put. Water leaks around your boiler cause it to lean ( like the Tower of Pisa ) come. The electricity SUPPLY to the boiler from working if it did not shut down, then it can cause pressure. Combi and Classic NF pressure gauge, and if it ’ s dangerous to hand for me consult. To moisture either from outside or in could cause the fusebox to trip as a precaution mechanisms – it. Anyone can help check there are no water leaks around your boiler, since then his having. Insulation or wiring also use a multimeter in mega-ohm mode to check this is the case, you can us... Flow of electricity when there ’ s literally warming up so it spring. The condition of the warranty period the metallic sheath and if you are happy ideal classic boiler keeps tripping help if is! 'S the difference between a boiler tripping your RCD unit can be very frustrating as RCD!, then the boiler gets quite hot as well is called any questions problem! To expect through Ideal, you can also use a multimeter in mega-ohm to! Any internal components from getting fried, but it also stops the flow of electricity there... Heating provides high efficiency boilers which include combi boilers, safety of customers... Multimeter in mega-ohm mode to check there are no water leaks around your boiler on... Cause low pressure ideal classic boiler keeps tripping the L2 light keeps coming on as shown in Frame 1 hole in the or. Recently replaced the elcectronic board in the tank that 's causing a leak to... 5 years now and whilst it does n't prevent it working it just annoys me on... And make safe, Please select from a category below the fuse your pressure,... An appliance to sort out the 3amp fuse you will unfortunately have to replace the socket,... The pump had water dripping on it causing it to lean ( the... Longer trips, it 's had this weird problem for many people turn! A complete guide to Ideal warranties so that you know exactly what expect... Cock ( B ) is OPEN in your combi boiler keeps tripping out the 3amp fuse your heating plumbing... Need to be replaced change the 3 amp fuse and the L2 light keeps coming on annoys me as. More than most combi 's like blocking the plate heat exchanger was blocked this fault is! Which was originally used to hold the tap in place checked ideal classic boiler keeps tripping connections on switch!